工程建设标准英文版
建筑电气照明装置施工与验收规范(英文版) GB 50617-2010 现行
Code for Construction and Acceptance of Electrical lighting Installation in Building GB 50617-2010 收藏

发布日期:2010-08-18

实施日期:2011-06-01

主编部门:

主编单位:Ningbo Construction Co.,Ltd.,Zhejiang Industry Equipment Installation Group,Co.,Ltd.

主要起草人:Xie Zhenmiao,Fu Ciying,Shen Lien,Shen Zhiqiao,Wang Zhensheng,Qian Dazhi,Zhu Yuezhong,Wu Ruili,Tan Junhui,Liu Boping,Zhang Haiyun

出版社:中国建筑工业出版社

标准书号:GB 50617-2010

出版时间:2014-09-01

售价 108.00

During the development of this code,the development group examined and finalized this code based on wide investigation and research,careful summary on practical experiences,with reference to relevant international standards,as well as extensively solicited opinions.

This code is applicable to the construction,handover and acceptance of the installation project of electrical lighting installations in industrial and civil buildings as well as in structures.

According to the requirements of Document JIANBIAO[2008] No.105 issued by the Ministry of Housing and Urban-Rural Development-Notice on Printing the Development and Revision Plan of National Engineering Construction Standards(2Batch)in2008,this code was jointly developed by Ningbo Construction Co.,Ltd.,Zhejiang Industry Equipment Installation Group,Co.,Ltd.and other organizations concerned.

During the development of this code,the development group examined and finalized this code based on wide investigation and research,careful summary on practical experiences,with reference to relevant international standards,as well as extensively solicited opinions.

This code comprises 8 Chapters with the main technical contents of:general provisions,terms,basic requirement,luminaires,socket,switch,fan,lighting distribution box (panel),pre-operational test and measurement of electrifying as well as handover and acceptance of project.

The provisions printed in bold type in this code are compulsory ones and must be enforced strictly.

Ministry of Housing and Urban-Rural Development is in charge of the administration of this code and the explanation of the compulsory provisions.Ningbo Construction Co.,Ltd.is responsible for the explanation of specific technical contents.During the process of implementing this code,the relevant opinions and advice,wherever necessary,can be posted or passed on to Ningbo Construction Co.,Ltd.at any time (Address:No.46,Xingning Road,Ningbo,315040) for future reference in revision.

Chief Development Organizations,Participating Development Organizations,Participating Organizations,Chief Drafting Staff and Chief Examiners of this code:

Chief Development Organizations:

Ningbo Construction Co.,Ltd.

Zhejiang Industry Equipment Installation Group,Co.,Ltd.

Participating Development Organizations:

Shanghai Installation Engineering Co.,Ltd.

Guangdong Industrial Equipment Installations Company

Ningbo Second Equipment Installation Co.,Ltd.

Hangzhou Construction Quality and Safety Supervision Head Station

General Station for Safety and Quality Supervision of Building Engineering of Ningbo

Illuminating Engineering Society of Beijing

Participating Organization:

Ningbo University of Technology

Chief Drafting Staff:

Xie Zhenmiao Fu Ciying Shen Lien Shen Zhiqiao Wang Zhensheng Qian Dazhi Zhu Yuezhong Wu Ruili Tan Junhui Liu Boping Zhang Haiyun

Chief Examiners:

Wen Boyin Yu Licheng Zhou Weixin Zhang Xinyue Liu Wenshan Huang Shangmin Zhai Xiaoming Lian Guanzhang Li Yunjiang

Announcement of the Ministry of Housing and Urban-Rural Development of the People's Republic of China

No.753

Announcement on Publishing the National Standard Code for Construction and Acceptance of Electrical Lighting Installation in Building

Code for Construction and Acceptance of Electrical Lighting Installation in Building has been approved as a national standard with a serial number of GB 50617-2010 and shall be implemented from June 1,2011.Therein,Articles (Items) 3.0.6,4.1.12,4.1.15,4.3.3,5.1.2 (1,2,and 3) and 7.2.1 are compulsory provisions and must be enforced strictly.

Authorized by the Standard Rating Research Institute of the Ministry of Housing and Urban-Rural Development of the People's Republic of China,this code is published and distributed by China Planning Press.

Ministry of Housing and Urban-Rural Development of the People's Republic of China

August 18,2010

目录

Announcement of the Ministry of Housing and Urban-Rural Development of the People's Republic of China

Foreword

1 General Provisions

2 Terms

3 Basic Requirement

4 Luminaires

4.1 General Requirement

4.2 Luminaires for Common Use

4.3 Luminaires for Special Use

5 Socket,Switch and Fan

5.1 Socket

5.2 Switch

5.3 Fan

6 Lighting Distribution Box (Panel)

7 Pre-operational Test and Measurement of Electrifying

7.1 Pre-operational Test of Electrifying

7.2 Measurement of Illuminance and Lighting Power Density

8 Handover and Acceptance of Project

Explanation of Wording in This Code

List of Quoted Standards

3.0.6 It is strictly forbidden to install and fix electrical lighting installations with wooden wedge,nylon plug or plastic plug on the masonry and concrete structures.

4.1.12 The uncharged and exposed conductive parts of Class I luminaire must be reliably connectedwith protective earthing(PE)and shall be marked.

4.1.15 For the luminaire with a mass of greater than 10kg, strength test for 15 min shall beconducted according to the total number of constant uniform loads of 5 times of luminaire mass on the fixing device.The parts of fixing device shall be free from obvious deformation.

4.3.3 The landscape lighting luminaire of the building shall meet the following requirements:

1 Where the luminaires are installed in the locations with dense people passing by, such as sidewalk, and no fence protection is provided, the height from luminaire bottom to the ground shall be more than 2.5m;

2 Luminaire and its metal frame and metallic protection tube shall be reliably connected with the protective earth wires (PE) and shall be marked;

3 Energy efficient grade of luminaire shall meet the design requirements.

7.2.1 With illuminance and lighting power density test requirements, the average illuminance andlighting power density value in the tested zone shall be measured and recorded without external light source and each kind of functional zone shall be inspected at no less than two positions.

1 Illuminance value shall not be less than the design value;

2 Lighting power density value shall meet the requirements of the current national standard GB 50034 or the design requirements.